Skip to content

Pipe insulation – BetaPlus “Phenolic pipe section”

Other risk levels Fire

Published by Safety Gate 14 Dec 2015In the weekly report of 18 Dec 2015 (week 50, 2015)Safety Gate noticeJSON
latest report: week 43, 30 Oct 2026checked 3 min agoSource: EU Safety Gate
Product
Pipe insulation
Brand
BetaPlus
Name
Phenolic pipe section
Type / model
Pipe insulation diameters 15mm to 300mm
Batch
All CE marked product manufactured from 1 July 2013 to 10 June 2015
Description
Thermal foam pipe insulation coated with aluminium foil that is glued to the foam to provide a vapour barrier and is chemically coated. The insulation is used for heating, ventilation and air conditioning, and is suitable for copper, steel and plastic pipe work. Supplied in a cardboard box.
Risk
null Persons in commercial building where product is used are not able to escape from the building because the reaction to fire properties of the product is D or worse (if not fitted correctly) when claimed to be class B. Thus the product does not slow down the spread of fire in the building, particularly in any open emergency escape stairways with exposed HVAC (heating, ventilation, and air conditioning) piping.
Measures
  • - · by the manufacturer · from 1 Sep 2015
Notifying country
United Kingdom
Country of origin
United Kingdom
Alert type
Professional
Photos
Photo 1 of the product in Safety Gate alert A11/0116/15Photo 2 of the product in Safety Gate alert A11/0116/15
Photos shown from the Safety Gate server (European Commission); not copied here.

This page reproduces the Safety Gate record as published. recallarchive is not affiliated with the European Commission. If you own this product, follow the measures above and contact the seller.

Sources

  1. Safety Gate alert A11/0116/15
    European Commission, Safety Gaterecord fields marked “official alert record”: © European Union, CC BY 4.0; values listed separately here
  2. Safety Gate weekly report Report-2015-050 (XML)
    the copy this page was built fromCC0 1.0